FIRE

“  Fire is the chemical reaction in which fuel ,oxygen and heat which produce flame is called as fire”.
CLASSIFICATION OF FIRE-
·        CLASS ‘A’-  Solid Fire  -  Wood
·        CLASS ‘B’-  Liquid Fire -  Petrol
·        CLASS ‘C’-  Gas Fire     -  Mithen
·        CLASS ‘D’ – Metal fire -  Magnesium
·        CLASS ‘E’ – Electrical fire
TYPES OF EXTINGUISHER
1.     Water type extinguisher.
2.     COtype extinguisher.
3.     DCP type extinguisher.
4.     Soda acid extinguisher.
5.     Fome type extinguisher.
CAUSES OF FIRE
·        Faulty electrical equipment or wiring.
·        Poor housekeeping.
·        Over loaded electrical system.
·        Over heating of equipment or servers.
·        Careless handling of fire like disposal cigarettes naked flamed, inflammable materials etc
·        Spontaneous combustion (sun / direct heat)

FIRE FIGTHING SYSTEM

SR.NO
DESCRIPTION
AS PER NBC 2005
PART
DESIGN AS PER APOSTLE
1
Type of building
Residential building
Type:A-4 apartment

2
Height of building
Above 60m

3
Fire Extinguishers
Required
Provided
4
Hose reel
Required
Provided
5
Dry Riser
Not required
Not provided
6
Wet Riser
Required
Provided
7
Down corner
Not required
Provided
                         









 


8
Yard Hydrant
Required
Provided
9
Automatic sprinkler system
Required
Provided in common areas and basements
10
Manually operated electrical  alarm system
Required
N/A, as automatic detection system is proposed
11
Automatic detection alarm system
Required
Provided as per NBC
12
Under ground water storage(static)tank
100,000
Provided 200000 litres

13
Terrace tank
25,000
Provided on each block
14
Pump capacity near underground static water storage tank (fire pump)with minimum pressure of 3.5 kg/sq.cm at terrace level
1.Two electrical pumps 2850LPM
2.One diesel pump 2850LPM
3.Two electrical jockey pumps -180LPM

1. Provided 2nos multistage, multi outlet main fire pumps for hydrants and sprinkler system.
2. Provided
3. 2nos electrical jockey pump provided, one for lower zone and other for upper zone.

15
Pump capacity at the terrace tank level within minimum pressure of 2.0 kg/sq.cm
Not required
Provided 1no fire pump.




Fire fighting system has been designed as per NBC and by local Bylaws. If any areas is not covered by NBC, it shall be designed as per NFPA and local codes.

Fire Hydrant system shall cover the internal & external hydrants connected to the common fire Fighting through main hydrant lines. It is proposed to providing automatic sprinkler system for basement & all upper floors.

POWER REQUIREMENT FOR PLUMBING, DRAINGE AND FIRE FIGHTING SYSTEM PHASE:

SR.NO
ITEM
QTY
W=WORKING
SB=STANDBY
H.P.
EACH
TOTAL H.P.
1.
Fire Hydrant Pump-Dead load
1 NO
125
(125)
2.
Sprinkler pump-Dead load
1 NO
125
(125)
3.
Jockey pump for lower zone
1 NO
7.5
7.5
4.
Jockey pump for upper zone
1 NO
10
10

5.
Fire pump terrace
4 NOS
40
(40)
6.
Domestic water transfer from
2 NOS
(1 W+1 SB)
20
20
7.
Domestic Hydro-pneumatic system at terrace level
4 NOS
3
12
8.
Flushing water transfer pump
2 NOS
(1 W+1 SB)
10
10
9.
Irrigation water pump
2 NOS
(1 W+1 SB)
10
10
10.
Sewage Treatment plant
L.S.
85
85